  • Standard:    UL 864

    Supply Voltage (S-SC):    25.3 ~ 39 VDC

    Auxiliary Supply Voltage:    18.8 ~ 27.2 VDC

    Average Current Consumption (On S-SC Line):    670μA

    2-Wire Detector Loop Current Standby Detector Load:    1mA Max.

    From Auxiliary Supply:    60mA Max.

    EOL Device:    4.7K ohms Resistor

    Max. Quantity Per Loop:    127

    Max. Quantity Per Loop:    127

    Alarm Threshold Level:    < 1.5K ohms

    Alarm Threshold Level:    < 1.5K ohms

    Wiring Threshold Level:    > 2.5K ohms & < 6K ohms

    Open Circuit Threshold Level:    > 10K ohms Max.

    2-Wire Conventional Detector (Loop Resistance):    50 ohms (total wire length)

    Dimensions:    4.2"W x 4.7"H x 1.4"D

    Operating Temperature:    32°F (0°C) ~ 120°F (49°C)

    Mounting:    4" square electrical box

    Relative Humidity:    90% RH Non-Condensing